PERFORMANCE GUIDELINES: 1. FOUNDATION/BASEMENT
1.6 Interior Concrete Floor Has Settled
Acceptable Performance/Condition
Minor settlement of concrete floors is not uncommon and is acceptable.
Where the interior floor meets a foundation wall, the concrete floor slab shall not settle more than 12 mm (1/2”) from its original position.
The above standard applies to finished and unfinished concrete floors within a new home. Floors serving attached garages or carports are dealt with later in this document.
Crawl space is excluded from this standard.Warranty Coverage
- 12 months In-Home
- 15 month Common Property
Claim Response
Slabs not meeting the Acceptable Performance/Condition are to be rectified.
Repair may include adding a topping, slab jacking or other industry accepted method.
Where repairs are made, colour, finish or texture of the repair may not match the surrounding concrete.