PERFORMANCE GUIDELINES: 1. FOUNDATION/BASEMENT
1.4 Exposed Interior Concrete Floor Slabs Are Uneven
Acceptable Performance/Condition
Exposed interior concrete floors shall not have bumps, ridges or depressions exceeding 12 mm (1/2”) within a 3 m (10') specified plane.
Concrete floors sloped to provide drainage is not considered to be a defect.
Crawl space skim coats are excluded from this guideline.
Warranty Coverage
- 12 months In-Home
- 15 month Common Property
Claim Response
Floor slabs not meeting the Acceptable Performance/Condition must be rectified.
Repairs may include grinding, applying a topping or other industry acceptable methods.
The colour, finish or texture of a repaired area may not match the surrounding concrete.